Psychrometric Calculator (Moist Air)

What are the wet-bulb, dew point, humidity ratio and enthalpy of this air?

Single calculationv1.0.0Verified 2026-11-01Runs in your browser

Spec sheet

ashrae_2017_psychrolib · v1.0.0
Method

ASHRAE Handbook — Fundamentals (2017) ch. 1, via PsychroLib

  1. 01p_ws: Hyland–Wexler (ASHRAE eqn 5, 6)
  2. 02W = 0.621945 · p_w / (p − p_w)
  3. 03h = 1.006·t + W·(2501 + 1.86·t) kJ/kg
  4. 04Wet bulb: bisection on ASHRAE eqn 33/35
  5. 05p(z) = 101325·(1 − 2.25577e−5·z)^5.2559
Limits — read before relying on it
  • Valid for −100 °C to 200 °C (ASHRAE fit range).
  • Ideal-gas mixture; ASHRAE notes the saturation-pressure fit is within 300 ppm of tabulated values.
  • Standard-atmosphere pressure for the altitude; enter weather-station pressure for exact work.